testing RCDs of types B / B+ (universal) and types AC, A, F (mixed frequencies)
even more easier, efficient and safer tests
Features
bidirectional interfaces (USB / RS 232)
measured value memory covering four levels (object / block / fuse / measuring point)
upload of installation structures and download of measured values
integrated real-time clock (measured value with date/ time)
unambiguous "PASS" / "FAIL" indication by means of green / red LED on the tester and on the switchable "Commander" probe tip
"Commander" probe tip with "TEST" and "MEM" key as well as bright LED measuring point illumination
all measuring functions can be selected directly by means of a rotary switch
memory of measured values for 1800 measurements
graphic display with background lighting, help function with connecting diagram
power supply by means of six NiMH storage batteries (AA)
device with integrated storage battery charging function
Measuring functions
low-impedance resistance of protective conductor and equipotential bonding conductor connections (testing current: 200 mA with polarity reversal)
insulating resistance with testing voltages of 50 / 100 / 250 / 500 / 1000 V
line impedance (L-N / L) with voltage drop and short-circuit current
loop impedance (L-PE) without RCD tripping and short-circuit current
testing of RCDs, standard and delayed (S), types AC, A, F, B, B+ with AUTO test, contact voltage, tripping time and tripping current (ramp test)
TRUE RMS voltage, frequency and phase sequence test
single-fault leakage current in IT networks
Measuring functions by means of optional accessories
earthing measurement by means of three-wire measuring method by means of earthing kit
TRUE RMS current by means of current clamps BENNING CC 1 / BENNING CC 3
luminous intensity by means of BENNING luxmeter type B
Specification
BENNING IT 130
Display
graphic display (illuminated)
Low-impedance resistance
0.01 Ω – 2 kΩ
Insulation resistance
0 kΩ – 1000 MΩ
line impedance (L-N / L)
0.01 Ω – 10 kΩ
loop impedance (L-PE)
0.01 Ω – 10 kΩ
Short-circuit current
0.01 Ω – 200 kA
RCD testing of types AC / A / F, B / B+ and EV / MI
tripping time, tripping current (ramp), contact voltage, automatic testing (AUTO)
Rotary field
Yes
Voltage (TRUE RMS), frequency
1 V – 550 V, 0 Hz – 500 Hz
Earth resistance
0.01 Ω – 2000 Ω (by means of earthing set)
Current (TRUE RMS)
0.1 mA – 400 A (by means of clamp)
luminous intensity
0.01 lux – 20 klux (by means of sensor)
Measured value memory
up to 1800 measuring results
Interfaces (bidirectional)
USB, RS 232
Incl. software
Yes
Scope of delivery
case, PC software, USB / RS 232 cabel, switchable "Commander" probe tip, testcabel with shock-proof plug, universal three-wire test cable (L = 1.5 m), 3 x test prob / crocodile clips, charger with 6 NiMH storage batteries (AA), calibration certificate