Products
ABB - AF190-30-11-13 Contactor

ABB - AF190-30-11-13 Contactor

Brand: ABB
Model No: AF190-30-11-13
$0.00
Qty: Add to Cart

The AF190-30-11-13 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 90 kW / 400 V AC (AC-3) or 125 hp / 480 V UL and switching power circuits up to 275 A (AC-1) or 250 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

 

Technical data

Number of Main Contacts NO:

3

Number of Main Contacts NC:

0

Number of Auxiliary Contacts NO:

1

Number of Auxiliary Contacts NC:

1

Rated Operational Voltage:

Main Circuit 1000 V

Rated Frequency (f):

Main Circuit 50 / 60 Hz

Conventional Free-air Thermal Current (Ith):

acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A

Rated Operational Current AC-1 (Ie):

(1000 V) 40 °C 250 A
(1000 V) 55 °C 225 A
(1000 V) 60 °C 225 A
(1000 V) 70 °C 185 A
(690 V) 40 °C 275 A
(690 V) 55 °C 250 A
(690 V) 60 °C 250 A
(690 V) 70 °C 200 A

Rated Operational Current AC-3 (Ie):

(415 V) 55 °C 190 A
(440 V) 55 °C 190 A
(500 V) 55 °C 156 A
(690 V) 55 °C 135 A
(1000 V) 55 °C 85 A
(380 / 400 V) 55 °C 190 A
(220 / 230 / 240 V) 55 °C 190

Rated Operational Current AC-3e (Ie):

(415 V) 60 °C 190 A
(440 V) 60 °C 190 A
(500 V) 60 °C 135 A
(690 V) 60 °C 135 A
(1000 V) 60 °C 85 A
(380 / 400 V) 60 °C 190 A
(220 / 230 / 240 V) 60 °C 190 A

Rated Operational Power AC-3 (Pe):

(415 V) 90 kW
(440 V) 110 kW
(500 V) 110 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW

Rated Operational Power AC-3e (Pe):

(415 V) 90 kW
(440 V) 110 kW
(500 V) 110 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW

Rated Breaking Capacity AC-3:

8 x Ie AC-3

Rated Breaking Capacity AC-3e:

8.5 x Ie AC-3e

Rated Making Capacity AC-3:

10 x Ie AC-3

Rated Making Capacity AC-3e:

12 x Ie AC-3e

Short-Circuit Protective Devices:

gG Type Fuses 355 A

Rated Short-time Withstand Current Low Voltage (Icw):

at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
Maximum Breaking Capacity:cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A

Maximum Electrical Switching Frequency:

(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour

Rated Operational Current DC-1 (Ie):

(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A

Rated Operational Current DC-3 (Ie):

(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A

Rated Operational Current DC-5 (Ie):

(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A

Rated Insulation Voltage (Ui):

acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V

Rated Impulse Withstand Voltage (Uimp):

Main Circuit 8 kV

Mechanical Durability:

5 million

Maximum Mechanical Switching Frequency:

300 cycles per hour

Coil Operating Limits:

(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)

Rated Control Circuit Voltage (Uc):

50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V

Coil Consumption:

Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 220 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 220 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 190 W

Operate Time:

Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms

Connecting Capacity Main Circuit:

Flexible 2 x 50 ... 95 mm²
Rigid Al-Cable 1 x 95 ... 185 mm²
Rigid Cu-Cable 1 x 6 ... 150 mm²

Connecting Capacity Auxiliary Circuit:

Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²

Degree of Protection:

acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00

Terminal Type:

Main Circuit: Bars